To ensure accurate test results for Group 31 batteries, the clamps are designed to connect to lead stud adapters (provided with the Micro700) or to the lead bases of threaded studs. (See Figures 1 and 2 on the next page.) Never connect the clamps directly onto the threaded studs.

Testing Individual Batteries
Every battery in the pack should be disconnected before testing. If the analyzer detects that the batteries are connected at the start of the Battery Pack Test, it will remind you to disconnect the pack.
To connect to batteries with threaded studs:
1. Screw the negative (–) terminal adapter onto the negative stud, and the positive (+) adapter onto the positive stud.
2. Connect the red clamp to the positive (+) adapter.
3. Connect the black clamp to the negative (–) adapter.
4. For a proper connection, rock the clamps back and forth. Both sides of the clamp must be firmly connected before testing (Figure 1). If the message CHECK CONNECTION appears, clean the terminals and/or reconnect the clamps.